The widespread use of power converters in low-voltage distribution grids has given rise to issues regarding the power quality. In fact, non-linear loads such as AC Drives, switching-mode power supplies and grid-connected converters can cause, besides the generation of several current harmonics, also a DC current component injection into the grid. This DC current component can lead to magnetic saturation of the distribution power transformers; in this condition, the transformers present distorted current waveforms, increased power absorption and overheating, that can damage the transformer insulations. This paper presents a way to diagnose the magnetic saturation by a non-direct measurement of the DC current component flowing in the power transformer. In other words, the proposed solution provides an information about the total DC injection produced by the sum of all the electric devices connected to the distribution power transformer. The DC current component causes a DC voltage drop across the parasitic resistance of the transformer's winding: sensing this DC voltage drop allows to evaluate the DC current component. A magnetic sensor was developed in order to obtain a great sensitivity, and the implemented closed loop control allowed to guarantee a good linearity with a high rejection ratio of the grid voltage variations. Simulation and experimental results confirm the effectiveness of the proposed approach.

A sensor to detect the DC bias of distribution power transformers / Buticchi, Giampaolo; E., Lorenzani. - (2011), pp. 63-70. (Intervento presentato al convegno Diagnostics for Electric Machines, Power Electronics & Drives (SDEMPED), 2011 IEEE International Symposium on tenutosi a Bologna nel 5-8 Sept. 2011) [10.1109/DEMPED.2011.6063603].

A sensor to detect the DC bias of distribution power transformers

BUTICCHI, Giampaolo;
2011-01-01

Abstract

The widespread use of power converters in low-voltage distribution grids has given rise to issues regarding the power quality. In fact, non-linear loads such as AC Drives, switching-mode power supplies and grid-connected converters can cause, besides the generation of several current harmonics, also a DC current component injection into the grid. This DC current component can lead to magnetic saturation of the distribution power transformers; in this condition, the transformers present distorted current waveforms, increased power absorption and overheating, that can damage the transformer insulations. This paper presents a way to diagnose the magnetic saturation by a non-direct measurement of the DC current component flowing in the power transformer. In other words, the proposed solution provides an information about the total DC injection produced by the sum of all the electric devices connected to the distribution power transformer. The DC current component causes a DC voltage drop across the parasitic resistance of the transformer's winding: sensing this DC voltage drop allows to evaluate the DC current component. A magnetic sensor was developed in order to obtain a great sensitivity, and the implemented closed loop control allowed to guarantee a good linearity with a high rejection ratio of the grid voltage variations. Simulation and experimental results confirm the effectiveness of the proposed approach.
2011
A sensor to detect the DC bias of distribution power transformers / Buticchi, Giampaolo; E., Lorenzani. - (2011), pp. 63-70. (Intervento presentato al convegno Diagnostics for Electric Machines, Power Electronics & Drives (SDEMPED), 2011 IEEE International Symposium on tenutosi a Bologna nel 5-8 Sept. 2011) [10.1109/DEMPED.2011.6063603].
File in questo prodotto:
File Dimensione Formato  
2011_SDEMPED_DC_Sensor.pdf

non disponibili

Tipologia: Documento in Post-print
Licenza: NON PUBBLICO - Accesso privato/ristretto
Dimensione 1.03 MB
Formato Adobe PDF
1.03 MB Adobe PDF   Visualizza/Apri   Richiedi una copia

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11381/2392953
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 6
  • ???jsp.display-item.citation.isi??? ND
social impact